No. Test equipment to be calibrated
or measured value/quantity
Measured or reproduced value
or range using our standards
Best measurement
capability
Remarks
1. Reproduction of insulation resistance 10 kohm ... 30 Gohm 0,10 % BMC up to 5 Mohm
2. Reproduction of line and loop resistance and PE continuity 0 ohm ... 1 kohm 0,52 % BMC at 1000 ohm
3. Reproduction of low resistances 0 ohm ... 1 kohm 0,26 % BMC at 1000 ohm
4. Reproduction of earth resistance      

a) four lead method 0 ohm ... 1,9 kohm 0,26 % BMC referred to measures value
  b) using one clamp 0 ohm ... 1,9 kohm 0,26 % BMC referred to measures value
  c) using two clamps 0 ohm ... 290 ohm 0,26 % BMC referred to measures value
5. RCD measurements      
  a) contact voltage 0 V ... 125 V 0,6 % BMC referred to measures value
  b) trip out time 18,1 ms ... 5 s 0,7 ms BMC referred to measures value
  c) tripping current 3 mA ... 3 A 1,3 % BMC at 100 mA
6. Reproduction of varistor over-voltage protection 0V ... 1000 V 0,10 % BMC referred to measures value
7. Leakage current 2 mA ... 7,7 mA 1,6 % BMC at 7,7 mA
8. Measurement of withstanding voltage      
  a) voltage 100 V ... 12 kV 0,22 % BMC referred to measures value
  b) current 50 µA ... 20 mA 0,30 % BMC referred to measures value
9. Voltage drop 0 V ... 10 V 0,52 % BMC referred to measures value
10. Reproduction of earth bond resistances 0,05 ohm ... 1 kohm 0,52 % BMC at 1 kohm
11. Reproduction of DC voltage 0 mV ... 1020 V 13 ppm BMC at 20 V
12. Reproduction of DC current 0 µA ... 30 A 84 ppm BMC at 20 mA
13. Reproduction of DC current for clamps 0 A ... 1500 A 0,50 % BMC at 1500 A
14. Reproduction of AC voltage 0 mV ... 1020 V 0,030 % BMC at 20 V
15. Reproduction of AC current 0 µA ... 30 A 0,074 % BMC at 20 mA
16. Reproduction of AC current for clamps 0 A ... 1500 A 0,26 % BMC at 1500 A
17. Reproduction of power 0 W ... 1500 kW 0,078 % BMC at 2500 W
18. Reproduction of four wire resistance 0 ohm ... 1500 Gohm 19 ppm BMC at 10 kohm
19. Reproduction of frequency 1,0 Hz ... 10 MHz 1,0 ppm BMC referred to measures value
20. Reproduction of capacity 1 nF ... 10 mF 0,28 % BMC at 100 nF
21. Measurement of DC voltage 0 mV ... 1000 V 0,004 % BMC at 10 V
22. Measurement of DC current 0 mA ... 3 A 0,056 % BMC at 100 mA
23. Measurement of AC voltage 0 V ... 750 V 0,090 % BMC at 100 V
24. Measurement of AC current 0 mA ... 3 A 0,14 % BMC at 1,0 A
25. Measurement of four wire resistance 0 ohm ... 100 Mohm 0,011 % BMC at 100 kohm